Mar 07, 2023
945
INTRODUCTION
Problem Description:
Auxiliary port does not function on GP-ISW-R. Customers are attempting to turn inverter off by applying 12 VDC to the remote. Feature is not working
Resolution:
Regarding to the Aux. Port on the GPISW-R-12, we have found the resistor value is incorrect in location R30.
Current resistor value is 47K5
Correct resistor value should be 18K2
Replace resistor.
Comments:
Resistor needs to be replaced and customers unit replaced once testing is complete. Future orders should not be affected.